Measuring transducer P20Z type is destined to a continuous conversion of the rms current value or alternating voltage without the constant component into a standard d.c. current or d.c. voltage signal.

The transducer output signal is galvanically insulated from the input signal and the supply.

Features:

  • input: 0…60 / 100 / 150/ 250/ 400 / 500 / 600 V a.c., 0…1 / 5 A a.c.,
  • output: 0/4…20mA, 0…10V.

External dimensions: 22,5 x 120 x 100mm
 

SPECIFICATIONS

Basic parameters:

input voltage

60, 100, 150, 250, 400, 500, 600 V a.c.

input current

1 A (X/1 A a.c.), 5 A (X/5 A a.c.)

output signal

0…5 mA Rload ≤ 2000 Ω
0…20 mA Rload ≤ 500 Ω
4…20 mA Rload ≤ 500 Ω
0…10 V Rload ≥ 500 Ω

response time

0.5 sek.

accuracy class

0.2

transducer preheating time

15 min.

Consumption:

in supply circuit

≤ 4 VA

in voltage circuit

≤ 0.6 VA

in current circuit

≤ 0.2 VA

Supply voltage

85… 253 V a.c./d.c. or
20… 40 V d.c. or a.c.

Protection level ensured:

by the housing

IP 50

from the terminal side

IP 20

Weight

0.125 kg

Overal dimensions

22.5 x 120 x 100 mm

Fitting

on a 35 mm rail

Maximal wire section

2.5 mm2 for executions with screw socket-plug terminals
1.5 mm2 for executions with inseparable screw terminals

Reference and rated operating conditions:

input signal

0…0.01…1.2 In; 0…0.01…1.2 Un

frequency of the input signal

45…65…500 Hz

supply

85… 253 V a.c./d.c. or
20… 40 V d.c. or a.c.

admissible peak factor:

current

2

voltage

2

ambient temperature

– 20…23…55ºC

storage temperature

– 25…+85ºC

relative humidity

≤ 95%
(inadmissible condensation)

external magnetic field

0…40…400 A/m

short duration overload

(5 s)

voltage input

2 Un (max.1000 V)

current input

10 In

working position

any

Additional errors:

In multiplicity of the class index:

from ambient temperature changes

< 0.5 k/10 K

external magnetic field

< 1 k

frequency of the input signal

< 1 k/100 Hz

Standards fulfilled by the transducer:
Electromagnetic compatibility:

noise immunity

acc. to EN 61000-6-2

noise emission

acc. to EN 61000-6-4

Safety requirements:

Acc.to EN 61010-1:

isolation ensured by the housing:

double

isolation between circuits:

basic

Pollution degree:

2

For working voltages in relation to the
ground up to 300 V
installation category:

III

For working voltages in relation to the
ground up to 600 V
installation category:

II

Altitude above sea level:

< 2000 m