BDS-Pro Battery Cell Voltage Monitoring System – Up to 24 Jars / Cells
$5,534.90
BDS-Pro Battery Cell Voltage Monitoring System – Up to 24 Jars / Cells
Manufacturer: Eagle Eye Power Solutions
Product Features
• 24/7/365 Battery Monitoring
• Comprehensive Battery Management Software
• Installation while systems are online
• Meets NERC and IEEE standard recommendations for battery
monitoring
• Patented ripple-removing algorithm to filter out noise from
measurements
• Injects minimal current for measurement
• Simple to install with custom, pre-assembled installation materials.
• Can be powered by AC or DC
- Description
- Size Guide
- Datasheet
Description
Description
BDS-Pro Battery Cell Voltage Monitoring System – Up to 24 Jars / Cells
The BDS-Pro Battery Cell Voltage Monitoring System is designed to measure the aging status of critical backup batteries by measuring and recording: system voltage, load current, unit voltage, internal resistance, and temperature.
The BDS-Pro is intended for use on vented lead acid (VLA), valve regulated lead acid (VLRA), and nickel-cadmium
(NiCad) battery systems.
The included Centroid 2 Battery Management Software records measured data for comprehensive trending analysis.
The BDS-Pro Battery Monitoring Solution is an accurate, user-friendly and economic solution for monitoring
systems using up to 24 cells/units.
Reduce maintenance costs, improve up-time and manage your battery assets effectively by using the BDS-Pro battery
monitoring solution for your system.
Protect yourself from battery failure – one of the leading causes of facility downtime with battery monitoring.
The BDS-Pro Battery Monitoring System is designed to monitor stationary battery systems with up to 24 cells/units. Measured parameters include string voltage, string current, cell voltage, cell/connection resistance, and temperature.
The BDS is a robust solution that can be deployed in a wide range of environments. Communication to Eagle Eye’s proprietary battery management software allows for email alerts during alarm outbreak, as well as detailed trending and reporting.
- 24/7/365 Battery Monitoring
- Installation and maintenance can be done while battery systems are online
- Meets IEEE and NERC standard recommendations for battery monitoring solutions
- Utilizes a patented ripple-removing algorithm for the most precise and repeated results in any environment
- Injects a minimal current, allowing the user to test their battery multiple times a day without adverse effects on your battery or battery monitoring system
- Simple to install with custom (to your batteries and site), pre-assembled installation materials
- Can monitor all your systems in real time with flexible expanding solutions
- Can be powered by AC or DC
BDS-Pro Battery Monitoring System Product Features:
• 24/7/365 Battery Monitoring
• Comprehensive Battery Management Software
• Installation while systems are online
• Meets NERC and IEEE standard recommendations for battery monitoring
• Patented ripple-removing algorithm to filter out noise from measurements
• Injects minimal current for measurement
• Simple to install with custom, pre-assembled installation materials.
• Can be powered by AC or DC
BDS-Pro Battery Management Software
• Displays and records string voltage, string current, cell/unit voltage, internal resistance, temperature
• Trending analysis of measured parameters on a string and cell/unit level with colored, easy to read graphs
• PDF and Excel reporting
• Detailed log of alarm outbreak history
• Email and SMS alerts
• Automatically record, save, & playback discharge & recharge events
Common Applications: Power Utilities & Distribution, UPS Systems, Telecom
BDS-Pro Battery Monitoring System Technical Specifications
Measurement Range | Battery Capacity: 5 – 6,000 Ah System Voltage: 0 – 900 VDC Load Current: ±999.9 A Unit Voltage: 1.2, 2, 4, 6, 8, or 12 Volts (up to 24 units max at any voltage) |
---|---|
Accuracy / Resolution | System Voltage: ±0.5% / 0.1 V Load Current: ±1% / 0.1 A Unit Voltage: ±0.5% / 0.01 V Internal Resistance: ±2% / 0.001 mΩ Unit Temperature: ±2% / 0.5°C |
Test Speed / Test Load | 4 seconds per cell / less than 2 amps AC per cell |
Measuring Interval | Adjustable from 10 min to once daily (cell/unit readings) |
Data Transfer | TCP/IP to proprietary software, Modbus |
Internal Storage | Approximately 2 weeks backup |
Operating Environment | Temperature: 0 – 65 °C (32 – 150 °F) RH: Under 80% |
Power Requirements | Input: 36 – 150 VDC / 100 – 240 VAC |
Dimensions | 195 x 270 x 55 mm (7.7 x 10.6 x 2.2 in.) |