Handheld Partial Discharge Detector – PDS-100
$12,816.75
PARTIAL DISCHARGE DETECTOR – PDS 100
Manufacturer: Doble Engineering
Product Code: TN-80000
The Doble PDS100 Partial Discharge Surveyor is a radio frequency interference (RFI) surveying tool that is designed for use in a live substation. Without the need for outages, the PDS100 can detect partial discharge (PD) in just a few seconds – making it an ideal tool for a condition based maintenance program. Whole substations can be quickly surveyed and analyzed by simply walking around HV apparatus and using the PDS100 to detect and identify sources of PD and external interference.
FEATURES AND BENEFITS
- Uses RFI technology to identify and locate defects
- Detect harmful PD by the electromagnetic energy emitted from the area of activity
- Compare reference baseline to readings from inside the substation
- Spectrum and time modes
- Store recordings in the instrument and later transfer to a PC for further analysis with PDViewer software
- Rugged, light-weight, hand-held instrument
- Safe and effective method for PD detection
- Non-invasive inspection method for substation surveys
- Use on a daily basis or during routine substation inspections together with other methods such as infrared scanning
- Cost-effective way to include PD detection in your condition based maintenance program
- Description
- Size Guide
Description
PARTIAL DISCHARGE DETECTOR – PDS 100

The Doble PDS100 Partial Discharge Surveyor is a radio frequency interference (RFI) surveying tool that is designed for use in a live substation. Without the need for outages, the PDS100 can detect partial discharge (PD) in just a few seconds – making it an ideal tool for a condition based maintenance program. Whole substations can be quickly surveyed and analyzed by simply walking around HV apparatus and using the PDS100 to detect and identify sources of PD and external interference.
FEATURES AND BENEFITS
- Uses RFI technology to identify and locate defects
- Detect harmful PD by the electromagnetic energy emitted from the area of activity
- Compare reference baseline to readings from inside the substation
- Spectrum and time modes
- Store recordings in the instrument and later transfer to a PC for further analysis with PDViewer software
- Rugged, light-weight, hand-held instrument
- Safe and effective method for PD detection
- Non-invasive inspection method for substation surveys
- Use on a daily basis or during routine substation inspections together with other methods such as infrared scanning
- Cost-effective way to include PD detection in your condition based maintenance program
TECHNICAL SPECIFICATIONS
POWER SUPPLY
- External supply External DC adaptor, 12 V @ 2 A
- DC adapter 85 – 264 V AC (47 – 63 Hz)/ 12 V DC
- Internal battery Li-Ion, 7.2 V, 6.6 Ah
- Battery life > 4 hours
DETECTION AND SWEEP FUNCTIONS
- Detector modes Peak, Average and Separate Peak and Average Mode(SPAM)
- Sweep modes Continuous, Counted and Single Mode
FREQUENCY
- Measurement range 50 MHz – 1000 MHz
AMPLITUDE
- Display unit X/Y-axis: ms – MHz / dBm
DATA STORAGE/ TRANSFER
- Internal SD-Card (fixed)
- External USB storage class compliant, including Memory stick
- Data Transfer USB A/B to and from computer
LCD SCREEN
- Size 132 x 100 mm / 5.20 x 3.94 in (W x H)
- Resolution 640 x 480 pixels, 256 colors
MECHANICAL
- Size 350 x 220 x 70 mm / 8.85 x 12.20 x 2.25 in (WxHxD)
- Weight 2.2 kg / 4.85 lbs
ENVIRONMENT
- IP classification IP64 with top covers closed, IP51 with top covers open
- Humidity 0 – 95% non-condensing
- Operating temp 0°C to + 50°C / 14°F to 122°F
- Storage temp -20°C to + 70°C / -4°F to 158°F
ACCESSORIES
- Duck Antenna
- DA 100 Directional Antenna
- Telescopic Antenna
- Whip Antenna
- TEV Probe
- HFCT
- UHF Space Sensor
- UHF Drain Valve Sensor DN50/DN80