MPI-507 Multi-function Meter
$1,906.48
MPI-507 Multi-function Meter
Manufacturer: SONEL
Manufacturer Ref No: WMGBMPI507
- Description
- Size Guide
- Technical Specification
Description
MPI-507 Multi-function Meter
Features of MPI-507 Multi-function Meter
- Measurement of short circuit loop parameters
- Measurement of short circuit loop impedance in networks with rated voltage: 220/380 V, 230 V/400 V, 240/415 V and frequency 45…65 Hz, operating voltage range: 180…460 V
- Indication of short circuit loop resistance R and short circuit loop reactance X
- Measurements of short circuit loop impedance with 15 mA current, without tripping the RCD circuit breaker
- Maximum test current: 7.6 A (at 230 V), 13.3 A (at 400 V)
- Testing RCD breakers of AC, A types
- Testing of prompt, short-delay and selective RCDs with rated current values 10, 15, 30, 100, 300, 500 mA
- Measurement of IA trip current and tripping time tA for currents 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
- RE and UB measurement without RCD tripping
- Extended AUTO function of RCD measurement, with the possibility of measuring ZL-PE with low current
- Measurement of IA and tA during one RCD tripping
- Earth resistance measurement
- Measurement with 3-pole method
- Insulation resistance measurement
- Test voltage 100 V, 250 V, 500 V
- Measurement of resistance of protective conductors and equipotential bondings
- Measurement of protective connections continuity with a ±200 mA current in accordance with EN 61557-4
- Autocalibration of test leads – any leads can be used
- Low current resistance measurement with sound signaling
- Phase sequence indication
Additional functions
- Checking the correctness of PE connection using a contact electrode.
- Measurement of voltage (0 … 500 V) and network frequency.
- Memory of 990 results.
- Wireless data transmission to a computer.
- Backlit keypad.
Simplicity and cutting edge technologies
Probably the world’s smallest meter with such a large number of measurement functions. The functions are selected with a rotary switch. Additional parameters are set with buttons located on the housing face. The settings are saved by the device even when the battery is completely discharged.
All buttons and the modular display have backlight, which significantly improves operation in low light. Large memory eliminates the need for taking notes during the measurements.
Inspection of electrical safety
This device may be used to inspect safety of electrical systems in households and industrial facilities. Its main advantage is quick measurement (just a few seconds!) of fault loop impedance in circuits with RCD.
Measurements can be easily automated with:
- auto mode of residual current devices (RCD) tests,
- the WS adapter that can be used for testing systems via standard 230 V sockets
Earth resistance measurement
The device is ideal for measurements of earthing installations in residential buildings. It allows you to check the quality of the earthing system using the 3-pole method. Together with earth resistance result, the meter shows the interference voltage and the resistance of the auxiliary RS and RH probes.
Increased resistance to environmental conditions
The meter will cope well in difficult environmental conditions. Protection against penetration of dust and water is ensured by a unique housing with a level of protection IP67.
Communication and software
You can easily transfer measurement data to your computer via Bluetooth wireless communication. In order to generate a report on measurements for electric shock protection, use Sonel Reports PLUS software. Saving the downloaded data to the simplest formats and printing is provided by free Sonel Reader software.
Technical Specification
Measurement functions | Measurement range | Display range | Resolution | Accuracy |
---|---|---|---|---|
Fault loop impedance | ||||
Fault loop ZL-PE, ZL-N, ZL-L | 0.13 Ω…1999 Ω acc. to IEC 61557 | 0.00 Ω…1999 Ω | from 0.01 Ω | ±(5% m.v. + 3 digits) |
Fault loop ZL-PE in RCD mode | from 0.5 Ω…1999 Ω acc. to IEC 61557 | 0.00 Ω…1999 Ω | from 0.01 Ω | from ±(6% m.v. + 5 digits) |
Measurements of RCD parameters | ||||
RCD tripping test and measurement of tripping time tA measuring current 0,5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn | ||||
general and short-time delay RCD | 0 ms…300 ms | 0 ms…300 ms | 1 ms | ±(2% m.v. + 2 digits) |
selective RCD | 0 ms…500 ms | 0 ms…500 ms | 1 ms | ±(2% m.v. + 2 digits) |
Measurement of RCD tripping current IA measuring current 0,3 IΔn…2,0 IΔn | ||||
for sinusoidal residual current (AC type) | 3.0 mA…500 mA | 3.0 mA…500 mA | from 0.1 mA | ±5% IΔn |
for unidirectional residual current and unidirectional with the 6 mA DC bias (type A) | 3.5 mA…420 mA | 3.5 mA…420 mA | from 0.1 mA | ±10% IΔn |
Earth resistance | ||||
3-pole method | 0.68 Ω…1999 Ω acc. to IEC 61557-5 | 0.00 Ω…1999 Ω | from 0.01 Ω | from ±(3% m.v. + 5 digits) |
Insulation resistance | ||||
Measuring voltage 100 V | 100 kΩ…99.9 MΩ acc. to IEC 61557-2 | 0 kΩ…99.9 MΩ | from 1 kΩ | ±(5% m.v. + 8 digits) |
Measuring voltage 250 V | 250 kΩ…199.9 MΩ acc. to IEC 61557-2 | 0 kΩ…199.9 MΩ | from 1 kΩ | ±(5% m.v. + 8 digits) |
Measuring voltage 500 V | 500 kΩ…599.9 MΩ acc. to IEC 61557-2 | 0 kΩ…599.9 MΩ | from 1 kΩ | ±(5% m.v. + 8 digits) |
Resistance of protective conductors and equipotential bondings | ||||
Measurement of resistance of protective conductors and equipotential bondings with ±200 mA current | 0.12 Ω…400 Ω acc. to IEC 61557-4 | 0.00 Ω…400 Ω | from 0.01 Ω | ±(2% m.v. + 3 digits) |
Measurement of resistance with low current | 0.0 Ω…1999 Ω | 0.0 Ω…1999 Ω | from 0.1 Ω | ±(2% m.v. + 3 digits) |
Phase sequence indication | in the same direction (correct), opposite direction (incorrect), UL-L voltage: 100 V…440 V (45 Hz…65 Hz) |