Portable Appliance Tester PAT-805
$1,583.81
PORTABLE APPLIANCE TESTER- PAT-805
Product code: EA-51528-0
manufacturer: Sonel S.A.
PAT-805 digital meter is used to measure the basic parameters of portable electrical equipment (power tools, white goods, etc.) which determine their safety: resistance of protective conductors, insulation resistance, continuity of connections, leakage current, power.
PAT-800 can be used to test the equipment performed in accordance with standards:
- EN 60745 – 1 Hand-held motor-operated electric tools. Safety. General requirements
- EN 61029 Safety of transportable motor-operated electric tools – General requirements
- EN 60335 – 1 Household and similar electrical appliances -Safety -Part 1: General requirements
- EN 60950 Safety of information technology equipment (IT Equipment)
- VDE 0701 – 1 Instandsetzun, Änderung und Prüfung elektrischer Geräte. Teil 1: Allgemeine Anforderungen.
- VDE 0702 Wiederholungsprüfungen an elektrischen Geräten
Basic functions:
- measurement of protective conductor resistance with the currents: 200 mA, 10 A, 25 A (protection class I),
- measurement of insulation resistance three measurement voltages: 100 V, 250 V and 500 V
- measurement of equivalent leakage current,
- measurement of PE leakage current,
- measurement of residual leakage current,
- measurement of touch leakage current,
- measurement of equivalent leakage current,
- measurement of power,
- measurement of current consumption,
- IEC lead test.
- Description
- Size Guide
- Vendor Info
- More Products
Description
PORTABLE APPLIANCE TESTER- PAT-805

PAT-805 digital meter is used to measure the basic parameters of portable electrical equipment (power tools, white goods, etc.) which determine their safety: resistance of protective conductors, insulation resistance, continuity of connections, leakage current, power.
PAT-800 can be used to test the equipment performed in accordance with standards:
- EN 60745 – 1 Hand-held motor-operated electric tools. Safety. General requirements
- EN 61029 Safety of transportable motor-operated electric tools – General requirements
- EN 60335 – 1 Household and similar electrical appliances -Safety -Part 1: General requirements
- EN 60950 Safety of information technology equipment (IT Equipment)
- VDE 0701 – 1 Instandsetzun, Änderung und Prüfung elektrischer Geräte. Teil 1: Allgemeine Anforderungen.
- VDE 0702 Wiederholungsprüfungen an elektrischen Geräten
Basic functions:
- measurement of protective conductor resistance with the currents: 200 mA, 10 A, 25 A (protection class I),
- measurement of insulation resistance three measurement voltages: 100 V, 250 V and 500 V
- measurement of equivalent leakage current,
- measurement of PE leakage current,
- measurement of residual leakage current,
- measurement of touch leakage current,
- measurement of equivalent leakage current,
- measurement of power,
- measurement of current consumption,
- IEC lead test.
Other:
- automatic measurement range selection,
- 990 memory cells for measurement results with option of uploading to a PC through a USB port or printing,
- professional software for data processing and reporting,
- cooperation with a barcode reader and printer,
- supports pendrive flash memory,
- large and clear graphic display with backlight,
- ergonomic operation.
SPECIFICATION
Measurement of protective earth conductor resistance I=200 mA
(protection class I)
| Display range | Resolution | Accuracy |
| 0,00…0,99 Ω | 0,01 Ω | ±(4% m.v. + 2 digits) |
| 1,00…19,99 Ω | ±(4% m.v. + 3 digits) |
- test current: ≥200 mA for R= 0,2…1,99 Ω
- upper limit adjustable in the 10 mΩ …1,99 Ω range with the 0,01 Ω resolution
- measurement time adjustable in 1…60 s range, with the 1 s resolution
Measurement of protective earth conductor resistance I=10 A
(protection class I)
| Display range | Resolution | Accuracy |
| 0…999 mΩ | 1 mΩ | ±(3% m.v. + 4 digits) |
| 1,00…1,99 Ω | 0,01 Ω |
- technical method
- test current: ≥10 A for R≤0,5 Ω
- limit adjustable in the 10 mΩ …1,99 Ω range with the 0,01 Ω resolution
- measurement time adjustable in 1…60 s range, with the 1 s resolution
Measurement of protective earth conductor resistance I=25 A
(protection class I)
| Display range | Resolution | Accuracy |
| 0…999 mΩ | 1 mΩ | ±(3% m.v. + 4 digits) |
| 1,00…1,99 Ω | 0,01 Ω |
- technical method
- measurement with sinusoidal current of the mains frequency, test current: ≥25 A for R≤0,2 Ω
- limit adjustable in the 10 mΩ …1,99 Ω range with the 0,01 Ω resolution
- measurement time adjustable in 1…60 s range, with the 1 s resolution
Measurement of L-N circuit resistance
| Display range | Resolution | Accuracy |
| 0…999 mΩ | 1 mΩ | ±(5% m.v. + 5 digits) |
| 1,00…4,99 Ω | 0,01 Ω |
- test voltage: 4…8 V AC
- short-circuit current: max. 5 mA
Measurement of insulation resistance
Measurement range according to IEC 61557 – 2 for:
- UN=100 V: 100 kΩ…99,9 MΩ
- UN=250 V: 250 kΩ…199,9 MΩ
- UN=500 V: 500 kΩ…599,9 MΩ
| UN | Display range | Resolution | Accuracy |
| 100 V | 0…1999 kΩ | 1 kΩ | ±(5% m.v. + 8 digits) |
| 2,0…19,99 MΩ | 0,01 MΩ | ||
| 20,0…99,9 MΩ | 0,1 MΩ | ||
| 250 V | 0…1999 kΩ | 1 kΩ | |
| 2,00…19,99 MΩ | 0,01 MΩ | ||
| 20,0…199,9 MΩ | 0,1 MΩ | ||
| 500 V | 0…1999 kΩ | 1 kΩ | |
| 2…19,99 MΩ | 0,01 MΩ | ||
| 20,0…599,9 MΩ | 0,1 MΩ |
- limit adjustable in the: 0.01…9.9 mA range with the 0.1 MΩ resolution
- adjustable measurement time: continuous measurement (Cont), or from 4 s to 3 min with 1 s resolution
- automatic discharge of the capacity of the tested device after measurement
- protection against measuring live devices
- output current max. 1.4 mA
Measurement of PE and residual leakage current:
| Display range | Resolution | Accuracy |
| 0,00…3,99 mA | 0,01 mA | ±(5% m.v. + 2 digits) |
| 4,0…19,9 mA | 0,1 mA |
- limit adjustable in the 0.01…9.9 mA range with the 0.01 mA/0.1 mA resolution
- adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution
- in the middle of the measurement time, the meter automatically switches the polarity at the measuring terminal and displays the greater value
Measurement of equivalent leakage current:
| Display range | Resolution | Accuracy |
| 0,00…3,99 mA | 0,01 mA | ±(5% m.v. + 2 digits) |
| 4,0…19,9 mA | 0,1 mA |
- limit adjustable in the 0.01…9.9 mA range with the 0.01 mA/0.1 mA resolution
- adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution
- open circuit voltage 25…50 V
Measurement of touch leakage current:
| Display range | Resolution | Accuracy |
| 0,00…4,999 mA | 0,001 mA | ±(5% m.v. + 3 digits) |
- limit adjustable in the 0.01…9.9 mA range with the 0.01 mA/0.1 mA resolution
- adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution
- current measurement band 20 Hz…100 kHz
Measurement of power S:
| Display range | Resolution | Accuracy |
| 0…999 VA | 1 VA | ±(5% m.v. + 3 digits) |
| 1…3,99 kVA | 0,01 kVA |
- adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution
Measurement of current consumption:
| Display range | Resolution | Accuracy |
| 0,00…15,99 A | 0,01 A | ±(2% m.v. + 3 digits) |
- adjustable measurement time: continuous measurement (Cont), or 1…60 s with 1 s resolution
Voltage measurement:
| Display range | Resolution | Accuracy |
| 187,0…265,0 V | 0,01 V | ±(2% m.v. + 2 digits) |
„m.v.” measured value
Conforms to the EMC requirements according to EN 61326 – 1:2006 and EN 61326 – 2-2:2006.
Electrical safety:
- insulation according to EN 61010 – 1 and IEC 61557
- measurement category: II 300 V acc.to EN 61010 – 1
- enclosure protection rating acc. to EN 60529: IP40
Other technical specification:
- power supply: 187…265 V, 50 Hz
- load current: max. 16 A (230 V)
- measurement results memory: 990 cells
- data transmission to PC: USB
- dimensions: 330 x 235 x 120 mm
- weight: about 4,75 kg
- operating temperature: 0…+40°C
- storage temperature: -20…+70°C
- humidity: 20…80%