Temperature & Standard Signal Transducer, P30U
$270.18
Temperature & Standard Signal Transducer, P30U
Manufacturer: LUMEL
Product Code: P30U
- Description
- Size Guide
Description
Description
PRODUCT DESCRIPTION
The output signal is galvanically isolated from the input signal and the power supply.
P30U has programmable measurement and additional functions.
Programming parameters can be realized with the use of buttons, via RS-485 interface and free e-con software or Ethernet or any web browsers via Ethernet interface.
Features of P30U parameters and functions:
- input: programmable
- thermocouples, resistance thermometers,
- 0…4/20 mA, +/- 20mA
- -5…20mV, +/- 75mV; +/-200mV
- 400, 2000, 5500 ohm
- RS485 Master or Slave
- output: programmable
- analog (current or voltage)
- 1 or 2 x relays
- digital RS-485
- display: LCD 2 x 8 characters with backilit,
- supply: 85..253 V a.c./d.c. or 20…40 V a.c./20…60 V d.c.
- conversion of the measured value into any output signal on the basis of the individual liner characteristics,
- conversion of the measured value by means of one of five implemented mathematical functions,
- conversion of the measured value on the basis of 21-point individual characteristics,
- additional 24V DC 30mA power supply switched on/off like an alarm (option)
- indication of exceeding the alarm values,
- programmable alarm and analogue outputs with a reaction to the selected input value (main input or RTC clock),
- real time clock with a clock power supply backup function in case of a transducer power supply loss,
- recording the signal input in programmed time periods in the internal memory and on SD/SDHC card (option),
- internal memory with the capacity of 534336 records,
- automatic decimal point setting,
- preview of configured parameters,
- access to parameters locked by a password,
- programming the measurement averaging time.
SPECIFICATIONS
Measured quantities and measuring ranges:
Input type |
Nominal |
Coefficiant |
Input type |
Range |
Minimal |
Voltage 10 V |
-10…10 V |
5 |
Thermocouple J type |
0…400°C |
1 |
Voltage 24 V |
-24…24 V |
10 |
-200…1200°C |
2 |
|
Current |
-20…20 mA |
10 |
Thermocouple K type |
0…400°C |
1 |
Resistance 400 |
0…400 Ω |
4 |
-200…1370°C |
2 |
|
Resistance 2000 |
0…2000 Ω |
2 |
Thermocouple S type |
0…1760°C |
2 |
Resistance 5500 |
0…5500 Ω |
2 |
Thermocouple N type |
-20…420°C |
1 |
Pt100 |
-200…850°C |
5 |
-200…1300°C |
1 |
|
Pt250 |
-200…650°C |
4 |
Thermocouple E type |
-40…260°C |
1 |
-200…850°C |
3 |
-200…1000°C |
2 |
||
Pt500 |
-200…180°C |
3 |
Thermocouple R type |
0…1760°C |
2 |
-200…850°C |
3 |
Thermocouple T type |
-200…400°C |
1 |
|
Pt1000 |
-200…250°C |
4 |
Thermocouple B type |
400…1800°C |
1 |
-200…850°C |
2 |
RS485 Master |
|
|
|
Ni100 |
-60…180°C |
1 |
|
|
|
Ni1000 |
-60…150°C |
2 |
|
|
|
Ni100-LG |
-60…180°C |
1 |
|
|
|
Ni1000-LG |
-60…180°C |
2 |
|
|
|
Cu100 |
-50…180°C |
1 |
RS485 monitor |
|
|
Voltage mV |
-5…20 mV |
1 |
|
|
|
-75…75 mV |
4 |
|
|
||
-200…200 mV |
4 |
|
|
||
Accuracy class = 0.1 with the excep% on of S, R and B thermocouples, where accuracy class = 0.5 |
|
|
Outputs |
|||
Output type |
Properties |
Remarks |
|
Analog |
Current: 0/4…20 mA, load resistance ≤ 500Ω |
accuracy class: 0,1 |
|
Relay |
1 or 2 relays; |
|
|
Supplying output |
24 V d.c. / 30 mA (option) |
|
|
Digital Interface |
|||
Interface type |
Transmission protocol |
Mode |
Baud rate |
RS-485 |
MODBUS RTU |
8N2, 8E1, 8O1, 8N1 |
4.8; 9.6; 19.2; 38.4; 57.6; 115.2; 230.4, 256 kbit/s |
External Features |
|||
Overall dimensions |
45 x 120 x 100mm |
|
|
Weight |
< 0.25 kg |
|
|
Protection on grade |
for housing: IP40 |
for terminals: IP10 |
|
Readout field |
LCD 2 x 8 |
|
|
Rated Operating Conditions |
|||
Power supply |
85..253 V a.c. 40..400 Hz |
Power consumption: < 5 VA |
|
Temperature |
ambient: -25…23…+55°C |
storage: -30…70°C |
|
Relative humidity |
25…95% |
inadmissible condensation |
|
Operating position |
any |
|
|
Safety and Compatibility Requirements |
|||
Electromagnetic compatibility |
noise immunity |
acc. to EN 61000-6-2 |
|
noise emissions |
acc. to EN 61000-6-4 |
||
Isolation between circuits |
basic |
acc. to EN 61010-1 |
|
Pollution level |
2 |
acc. to EN 61010-1 |
|
Installation category |
III |
||
Maximal phase-to-earth working voltage |
– for supply and measuring circuits 300V |
||
Altitude above sea level |
< 2000 m |
|