AC Parameter Digital Panel Meter, N20Z

$106.19

AC Parameter Digital Panel Meter, N20Z

Manufacturer: LUMEL

Product Code: N20Z

SKU: AMI-593-16

Description

PRODUCT DESCRIPTION

AC Parameter Digital Panel Meter, N20Z

The N20Z meter is a digital programmable panel instrument destined for measurements of a.c. voltages, a.c. currents, or frequency. The readout display is a LED display which enables the exposition of results in red, green or orange colour.

Parameters of the N20Z meter:

  • input:
    – a.c. current: 1 A, 5 A,
    – a.c. voltage: 100 V, 250 V, 400 V
    – frequency: 20…500 Hz.
  • 2 alarm outputs of OC type (4 types of alarms) signaled by highlight of the alarm index,
  • protection level ensured by the housing: IP65,
  • readout field: 5 three-colour LED displays of 14 mm height,
  • highlighted measuring units,
  • supply: 85…253 V a.c./d.c. or 20…40 V a.c./d.c.
  • overall dimensions: 96 x 48 x 64 mm.

For the configuration of the N20Z is destined LPConfig program. The meter must be connected with the PC computer through a PD14 converter.
Parameters which can be reprogrammed are as follows:

  • display colour, individually in three intervals,
  • thresholds of displayed overflows,
  • display precision of the result (decimal point),
  • highlight of the unit,
  • kind of the measured signal a.c. or a.c. + d.c. (True RMS),
  • averaging time of the measurement,
  • recounting of indications (individual characteristic),
  • two alarms of OC type operating in six working modes.

SPECIFICATIONS

Measuring ranges

INPUTS:

Measuring range of Un voltage:

1…100…120 V
2.5… 250…300 V
4… 400…480 V


input resistance > 2 MΩ

Measuring range of In current:

0.01… 1…1.2 A
0.05… 5…6 A

input resistance 50 mΩ ± 10%
input resistance 10 mΩ ± 10%

Frequency measusurement:
(in voltage range 24… 480 V)

20… 500 Hz
input resistance > 2 MΩ

Preheating time

30 min.

Intrinsic error (at manufacturer settings):

– voltage and current

± (0.5% of the range ±1 digit)
in the frequency interval
20… 500 Hz

– frequency

± (0.02% of the range ±1 digit)

Additional errors in rated operating conditions:

– from ambient temperature changes

(50% of the intrinsic error/10K)

Averaging time:

– voltage, current (programmable)

min 0.5s (1s by default)

– frequency (not programmable)

1s

Alarm outputs

outputs of O/C type
(30 V, 20 mA),
Passive outputs acc. to
EN 62053-31

Rated operating conditions:

– supply voltage

85…253 V a.c. (45…65 Hz) or d.c.
20…40 V a.c. (45…65 Hz) or d.c.

– ambient temperature

– 10…23…55ºC

– storage temperature

– 25… + 85ºC

– relative air humidity

< 95%
(condensation inadmissible)

– working position

any

Sustained overload capacity

120% Un, 120% In

Short duration overload capacity (3 s):

– voltage input

2 Un (< 1000 V)

– current input

10 In

Readout field

5-digit three-colour LED display:
– digit height: 14 mm,
– colours: green, orange, red,
– indication range: -19999…99999

Ensured protection level from frontal side

IP 65 acc. to EN 60529

Dimensions

96 x 48 x 64 mm (with terminals)

Panel cut-out dimensions

92+0.6 x 45+0.6 mm

Weight

< 0.25 kg

Power consumption

< 6 VA

Electromagnetic compatibility:

– noise immunity

acc. to EN 61000-6-2

– noise emission

acc. to EN 61000-6-4

Safety requirements acc. to PN-EN 61010-1:

– isolation between circuits

basic

– installation category

III
(for 400 V execution – category II)

– pollution degree

2

– maximal phase-to-earth working voltage:

 

– for supply circuit

300 V

– for measuring input

600 V – category II
600 V – category II

– for input destined for programming

50 V

Vendor Information