Digital Circuit Breaker Analyzer
$8,063.21
Digital Circuit Breaker Analyzer
Manufacturer: Vanguard Instrument
Model: CT-3500 S2
P/N: 9002-UC
Supplied with: Base unit with PC software, hook-up cables, shipping case, and built-in thermal printer. Printer uses TP3 paper.
- Description
- Size Guide
Description
Digital Circuit Breaker Analyzer
The CT-3500 S2 is Vanguard’s second generation, stand-alone, digital, microprocessor-controlled, circuit-breaker timer. It measures the elapsed time from the instant a breaker coil is energized to the instant of opening or closing of a circuit-breaker’s dry contacts. In addition to timing a breaker’s contact response time, the CT-3500 S2 can also time relays or other switching functions that use an initiating trigger voltage (24-300 Volts DC or AC). The timer-triggering voltage starts three independent electronic timers. Each timer is individually stopped by its respective dry-contact closing or opening. The CT-3500 can fully analyze the timing of all circuit breaker operations (Open, Close, Open – Close, and Close – Open). Timing results are displayed in milli-seconds and cycles on the unit’s back-lit LCD screen and can be printed on the built-in 2.5-inch wide thermal printer.
- Detect Main & Insertion Resistor Contacts on same input
- USB computer interface
- USB Flash drive interface (Flash drive not included)
- Store 128 test records internally
- Initiate Breaker Operation
- Built-in 2.5″ wide Thermal Printer
- Rugged “QWERTY” style membrane keypad
Contact Timing Inputs
The CT-3500 S2 features three dry-contact, timer-channel monitoring inputs. The dry-contact channel power supply is fuse-protected. All inputs are shunted to ground until the instant a test is initiated. All contact timing inputs are protected against static discharge. A contact self-test cable-mode is also available for testing cables or connections to the breaker.
User Interface
The CT-3500 S2 features a back-lit LCD screen (128 x 64 pixels) that is viewable in both bright sunlight and low-light levels. A rugged, 44-key, “QWERTY” membrane keypad is used to control the unit and input data. The unit’s built-in 2.5-inch wide thermal printer can be used to print test reports.
Internal Test Record Storage
The CT-3500 S2 can store up to 128 test records in Flash EEPROM. Test records can be retrieved and printed on the built-in thermal printer, or they can be transferred to a PC via the unit’s USB interface. The USB interface can also be used for diagnostic testing and for updating firmware. The CT-3500 S2 also features a USB Flash drive interface that can be used to store test records on an external USB Flash drive.
A Windows®-based Circuit Breaker Analysis application is provided with each unit and can be used to transfer test records to a PC. Test records can also be reviewed, printed or exported in Excel, PDF, and XML formats for further analysis