Programmable transducer for 3 phase power networks, P43
$331.20
Manufacturer: LUMEL
Product Code:P43
- Description
- Size Guide
- Vendor Info
- More Products
Description
Programmable transducer for 3 phase power networks, P43
Description of Programmable transducer for 3 phase power networks, P43
P43 is destined for the conversion of 3-phase, 3 or 4-wire power network parameters, in balanced or unbalanced systems.
Features:
- Inputs signals:
- current: 1A or 5A
- voltage: 100V or 400V
- Outputs
- 4 relays (signaling measured quantity overflows), without analog outputs
- 2 relays, 2 analog outputs
- 4 analog outputs, without relay outputs
- Pulse output (control of 3-phase active energy consumption),
- RS-485 and USB interfaces with Modbus protocol,
- Built-in memory for the 15 minutes’ power profile,
- Storage of maximal and minimal values,
- Galvanic isolation,
- Programmable current and voltage transformer ratios,
- Transducer programming realized by means of a free LPCon or E-Con softwares,
- Overall dimensions: 90 x 120 x 100 mm.
SPECIFICATIONS
Measuring ranges and admissible basic errors
|
Measured |
Measuring |
L1 |
L2 |
L3 |
Σ |
Intrinsic error |
|
Current 1/5A |
0.02…6 A~ |
• |
• |
• |
|
± 0.2% |
|
Voltage L-N |
2.9…276 V~ |
• |
• |
• |
|
± 0.2% |
|
Voltage L-L |
10…480 V~ |
• |
• |
• |
|
± 0.5% |
|
Frequency |
45.0…66.0 Hz |
• |
• |
• |
|
± 0.2% |
|
Active power |
-1.65 kW…1.4 |
• |
• |
• |
• |
± 0.5% |
|
Reactive power |
-1.65 kvar…1.4 |
• |
• |
• |
• |
± 0.5% |
|
Apparent power |
1.4 VA…1.65 |
• |
• |
• |
• |
± 0.5% |
|
Tangens j |
-1.2…0…1.2 |
• |
• |
• |
• |
± 1% |
|
PF factor |
-1…0…1 |
• |
• |
• |
• |
± 0.5% |
|
Input active energy |
0…99 999 999.9 |
|
|
|
• |
± 0.5% |
|
Output active energy |
0…99 999 999.9 |
|
|
|
• |
± 0.5% |
|
Inductive reactive energy |
0…99 999 999.9 |
|
|
|
• |
± 0.5% |
|
Capacitive reactive energy |
0…99 999 999.9 |
|
|
|
• |
± 0.5% |
|
THD |
0…100% |
• |
• |
• |
|
5% |
Power consumption:
– in supply circuit ≤ 6 VA
– in voltage circuit ≤ 0.05 VA
– in current circuit ≤ 0.05 VA
|
Outputs |
|
|
Analog output |
0, 2 or 4 programmable outputs: |
|
Relay output |
0, 2 or 4 relays, |
|
Serial interface |
RS-485, USB |
|
Transmission protocol |
Modbus RTU |
|
Energy pulse output |
output of OC type, passive |
|
Impulse energy output |
O/C passive, acc. to EN 62053-31, |
|
Ratio of the voltage transformer Ku |
1.0…4000 |
|
Ratio of the current transformer Ki |
1…10000 |
|
Protection degree: |
|
|
– for the housing |
IP 40 |
|
– from terminals (rear side) |
IP 20 |
|
Weight |
0.3 kg |
|
Overal dimensions |
90 x 120 x 100 mm |
|
Fixing way |
on a 35 mm DIN rail |
|
Reference and rated operating conditions: |
|
|
– supply voltage |
85…253 V d.c./a.c., 40…400 Hz |
|
– input signal |
0…0.005…1.2In; 0.05…1.2Un for |
|
– power factor |
-1…0…1 . |
|
– analog output |
-24..-20…0…20…24 mA |
|
– ambient temperature |
-25…23…+55°C |
|
– storage temperature |
-30…+70°C |
|
– humidity |
25…95% |
|
– admissible peak factor: |
|
|
– current |
2 |
|
– voltage |
2 |
|
– external magnetic field |
0…400 A/m |
|
– short duration overload |
(5 s) |
|
– voltage inputs |
2Un (max.1000 V) |
|
– current imputs |
10 In |
|
– working position |
any |
|
– preheating time |
5 min. |
|
Additional errors: |
|
|
In percentage of the intrinsic terror: |
< 50% |
|
– from ambient temperature changes |
< 50%/10°C |
|
Standards fulfilled by the meter |
|
|
Electromagnetic compatibility: |
– noise immunity acc. to EN 61000-6-2 |
|
Safety requirements: – (According to EN 61010-1 standard) |
|
|
– isolation between circuits: |
basic, |
|
– installation category: |
III, |
|
– pollution level: |
2, |
|
– maximal phase-to-hearth voltage: |
300 V |
|
– altitude above sea level: |
< 2000 m |