SIGNAL TRANSMITTER – CTI-01/S (housing IP56, wall installation)

SIGNAL TRANSMITTER – CTI-01/S (housing IP56, wall installation)

MANUFACTURER: STEIEL ELETTRONICA Srl

CAT NO: CTI-01/S

SKU: EA-1122-5

Description

SIGNAL TRANSMITTER – CTI-01/S (housing IP56, wall installation)

SIGNAL TRANSMITTERS - CMK-ADPP

The CMK50 cell uses the inductive working principle to perform conductivity measurements of liquids, up to 500 mS/cm. The cell can be installed in immersion or in a flow-through probe-holder. Moreover, mounting (PP or steel) accessories for in-line installation. Principle of operation: the cell is built with two internal electrical coils, transmitter and receiver.

When the transmitter winding is solicited by a suitable electric current, it generates a magnetic field, which create an electric current in the liquid, proportional to the specific conductivity of the measured fluid. This current is detected by the receiver winding. Furthermore, a specific inbuilt sensor detects the liquid temperature and automatically thermo-compensates readings, providing the final actual value of the fluid conductivity

TECHNICAL FEATURES

  • Measurements with inductive method, up to 500 mS/cm
  • PEEK body with ½” threading
  • Operating temperature: max 120 °C
  • Inbuilt temperature sensor for thermo-compensated readings
  • Standard cable: 10 meters
  • Immersion or flow type installation with proper probe holders
  • In-line installation with mounting accessories in PP or stainless steel
  • Signal transmitter with 4-20 mA output, to be ordered according to the needed measurement range

MODELS

  • Signal transmitter, 230V~, output 4-20 mA, range up to 5 mS/cm
  • Signal transmitter, 230V~, output 4-20 mA, range up to 10 mS/cm
  • Signal transmitter, 230V~, output 4-20 mA, range up to 20 mS/cm
  • Signal transmitter, 230V~, output 4-20 mA, range up to 50 mS/cm
  • Signal transmitter, 230V~, output 4-20 mA, range up to 100 mS/cm
  • Signal transmitter, 230V~, output 4-20 mA, range up to 200 mS/cm
  • Signal transmitter, 230V~, output 4-20 mA, range up to 500 mS/cm
  • Cell Body: PEEK
  • Installation: ½” G connection; immersion or down-flow probe holder
  • Thermo-compensation: automatic, through inbuilt sensor
  • Working Temperature: max 120°C
  • Cable: 10 m
  • Connection: via proper signal transmitter (CTI-01 series)